| Complete with: | iron core 3 phase reactors for harmonic contaminated environments HRC fusing ventilation kit NEMA 3R galvanized enclosure |
| Options | blown fuse indicators LED current indicators contactors, c/w: pre-charge coils NEMA 1, 2, or 12 galvanized enclosures powder coated enclosures |
| Manufactured by | Vishay Electronic GmbH (Roederstein), Germany |
| Voltage Ratings | 240 – 999 V |
| Maximum kVAr per 3 phase casing (60 Hz) | 13.6 kVAr @ 208V (rated 16.3 kVAr @ 240V)25.0 kVAr @ 480V (rated 30.0 kVAr @ 525V)25.0 kVAr @ 600V (rated 33.0 kVAr @ 690V)10.0 kVAr @ 600V (rated 28.0 kVAr @ 999V) |
| Specifications | UL and cUL, CSA CAN3-C155-M84 (1986),CSA C22.2 No. 190-M1985,IEC Publication 831-1, 831-2,VDE 560-47, 560-47, EN60831-1, EN60831-2 |
| Insulation (wet and dry options) | wet, ‘Ro’ series:non-PCB, natural oil impregnant, flash / ignition points 285/315°Cdry, ‘Rg’ series: non-PCB, dry / gas agent‘Ro’ and ‘Rg’ series are both biodegradable and non-toxic. |
| Electrodes | vacuum-metallized on one side of the plastic film |
| Ambient Temperature | -40°C to +45°C; storage temperature -40°C to +60°C |
| Inrush Current | maximum 300 times rated current |
| Loading Capacity | 1.10 times rated voltage1.30 times rated current1.50 times rated output |
| Frequency Ratings | 50 or 60 Hz |
| Capacitor Casing | seamless aluminum |
| Losses | ≤ 0.25 Watts per kVAr |
| Discharge Resistors | 50V or less in one minute after disconnection of supply voltage |
| Dielectric | polypropylene film |
| Safety Features | self-healingover pressure tear-off fuse / pressure sensitive circuit interrupter / internally fused up to 10kAIc, grounding / mounting stud at base of capacitor for easy mounting / replacement |
| Special Applications | designed for use in harmonic filters |
Documentation