Complete with: | iron core 3 phase reactors for harmonic contaminated environments IEC rated contactors, c/w: HRC fusing and inrush current limiters ventilation kit for maximum ambient temperature of 35°C (95°F) digital microprocessor controller and split core current transformer NEMA 1 ASA 61 grey enclosure |
Options | blown fuse indicators disconnect device NEMA 2, 3R, or 12 enclosure custom enclosure paint options custom enclosures for dimension restrictions |
Manufactured by | Vishay Electronic GmbH (Roederstein), Germany |
Voltage Ratings | 240 – 999 V |
Maximum kVAr per 3 phase casing (60 Hz) | 13.6 kVAr @ 208V (rated 16.3 kVAr @ 240V)25.0 kVAr @ 480V (rated 30.0 kVAr @ 525V)25.0 kVAr @ 600V (rated 33.0 kVAr @ 690V)10.0 kVAr @ 600V (rated 28.0 kVAr @ 999V) |
Specifications | UL and cUL, CSA CAN3-C155-M84 (1986),CSA C22.2 No. 190-M1985,IEC Publication 831-1, 831-2,VDE 560-47, 560-47, EN60831-1, EN60831-2 |
Insulation (wet and dry options) | wet, ‘Ro’ series:non-PCB, natural oil impregnant, flash / ignition points 285/315°Cdry, ‘Rg’ series:non-PCB, dry / gas agent‘Ro’ and ‘Rg’ series are both biodegradable and non-toxic |
Electrodes | vacuum-metallized on one side of the plastic film |
Ambient Temperature | -40°C to +45°C;storage temperature -40°C to +60°C |
Inrush Current | maximum 300 times rated current |
Loading Capacity | 1.10 times rated voltage1.30 times rated current1.50 times rated output |
Frequency Ratings | 50 or 60 Hz |
Capacitor Casing | seamless aluminum |
Losses | ≤ 0.25 Watts per kVAr |
Discharge Resistors | 50V or less in one minute after disconnection of supply voltage |
Dielectric | polypropylene film |
Safety Features | self-healingover pressure tear-off fuse / pressure sensitive circuit interrupter / internally fused up to 10kAIc, grounding / mounting stud at base of capacitor for easy mounting / replacement |
Special Applications | designed for use in harmonic filters |